Scenario note: The examples and exercises in this article are illustrative. They are not reports of confirmed Next Defence customer incidents.
A cloud support portal is still an OT boundary
A manufacturing or infrastructure operator uses a cloud-based supplier portal to reach industrial equipment for maintenance. The supplier calls it a SaaS tenant, but the actual exposure may run through site gateways, shared vendor accounts, remote desktop brokers and service identities that can issue commands to controllers. This checklist asks whether the operator can grant one approved maintenance task without granting the vendor persistent access to unrelated production areas. The first priority is safe operation: an access review must not disturb a running process or interfere with equipment protection systems.
Use a simulated site and representative gateway configuration. Define a permitted session as an authorised engineer viewing diagnostics for a named asset during an approved window. Define a prohibited session as the same supplier identity reaching a second plant zone, modifying an unauthorised setting or continuing after the work order closes. Read-only observation should be established at the industrial endpoint, not inferred from the wording on a cloud portal button.
Locate every point at which the vendor gains authority
Map the supplier's external account to identity federation, SaaS tenant roles, portal administrators, service accounts, site connector, jump server and controller-facing protocol. Record which organisation controls each component and how the operator can revoke access independently of the vendor. Check whether customer tenants share an administrative plane and whether a supplier technician is assigned to a customer, a plant, a device group or all managed equipment. A portal permission can be narrow while the downstream gateway has a standing high-privilege service credential.
Ask the operations engineer to identify the difference between viewing process telemetry, changing a configuration, sending a control command and downloading sensitive plant architecture. Treat these as separate capabilities. Maintenance may require temporary write permission, but a generic login that can reach every controller is difficult to justify. Consider whether the site connection initiates outward to the cloud, whether credentials are stored locally and what happens when the vendor platform is unavailable or compromised.
Put engineering change control in front of security testing
Agree on a test boundary with the plant manager, safety representative and technical custodian. Use a digital twin, isolated lab controller or known safe demonstration endpoint for negative command tests. No automatic scans, live isolation experiments or aggressive password trials should be directed at fragile industrial systems. ASD's OT guidance places safety and understanding of vital operations ahead of conventional IT convenience. Record approved maintenance windows, rollback conditions, isolation contacts and the status of alarms or fail-safe functions before running a technical demonstration.
The site engineer should know whether the proposed firewall change affects historian feeds, alarm aggregation, remote operator visibility or emergency vendor assistance. A blocked unsafe command is not an acceptable result if it also disables a safety-critical alert. If the dependency cannot be measured safely, stop the test and document a planned engineering review instead of taking a risk for the sake of a checklist score. That deferred work needs an owner and a date.
Verify a session from the customer's point of view
Create a fictional job ticket for a named asset, a named supplier engineer and an expiry. Confirm the engineer can authenticate, reach only the designated diagnostic endpoint and produce a site-visible session record. Then attempt a test against an unrelated synthetic asset and a disallowed command. Record the result at the receiving gateway or controller simulator, including the user, tenant, resource, action and decision. If a portal blocks the operation visually while the gateway accepts a direct protocol call, the boundary has not been demonstrated.
Repeat after the work order is closed, group membership is changed and the session token expires or is revoked. Check cached credentials and unattended gateway connections. If the provider supports recording remote sessions, confirm the operator can retrieve those records without making the supplier the only keeper of evidence. Distinguish a login to the SaaS tenant from an actual connection to a controller. The system should support attribution of commands, not merely a list of users who opened the portal that day.
Interrupt connectivity without losing operational awareness
The facilitator announces a suspected compromise of the cloud support identity. Operations needs telemetry, but the vendor says its portal cannot distinguish read-only visibility from remote maintenance. Compare measures such as disabling write commands at the site gateway, withdrawing a specific vendor account, restricting the approved work-order route, or stopping the remote connection after engineering approval. Each has different consequences for recovery. The plant owner should make the risk decision with a clear picture of what the control changes.
Next, simulate loss of the vendor's cloud service. Can local operators observe the plant, acknowledge alarms and retrieve necessary maintenance documentation? Is there an independently controlled emergency support route with strong authentication, local approval and an audit trail? A design that depends on a supplier's central cloud console for every safety-related intervention is a business-continuity concern even if remote access is technically encrypted. Record the safe fallback for sites with limited on-site engineering staff.
Review secrets, tenant separation and support contracts
Inventory certificates, API keys and service accounts used between the SaaS tenant and site connectors. Identify whether a shared supplier credential spans customers, whether secrets rotate, and how an old gateway is decommissioned. Customer-specific isolation needs enforcement at the target resource and the gateway. Reusing a vendor technician's corporate login across multiple clients is not enough to show that one client's access cannot cross into another. Include exported configurations, telemetry history and support attachments in the access review: these may contain sensitive diagrams or operating data.
Contracts should specify response contacts, revocation assistance, logging availability, support subcontractors and the process for emergency suspension. Ask whether the vendor can provide attributable records after the service has been disconnected. Keep a site-owned inventory of remote support paths rather than relying exclusively on the provider's list. A supplier renewal should prompt a repeat of the out-of-scope asset test, not merely an updated insurance certificate or questionnaire.
Use the checklist as a release gate
For each maintenance path, the acceptance packet should show the authorised job, asset, duration, engineer identity, permitted actions, site gateway policy, test record, failed negative request, safe disconnection method and recovery procedure. A control claim is demonstrated only when the protected endpoint or gateway enforces the expected decision and plant personnel can see what happened. If a feature cannot be verified without live risk, record it as not tested and use engineering-approved evidence or a simulation rather than manufacturing a pass.
Assign unresolved work separately: network segmentation to site engineering, cloud tenant privilege to the supplier-access administrator, session recording to operations, and contractual assurance to procurement. Retest after gateway firmware replacement, supplier personnel changes, a new plant zone, or a portal release that alters permissions. The result should be limited support that can be revoked at the site without threatening process safety or routine production.
Distinguish remote diagnostics from remote control
A supplier may argue that all its support sessions are read-only because the portal displays trends and alarms. Confirm what the site connector can actually send to equipment. Some protocols expose configuration writes, acknowledgements or operational commands under the same transport as diagnostic reads. Map supported functions per target asset and restrict them at a site-controlled enforcement point where feasible. The test should show the supplier retrieving a harmless simulated diagnostic and being denied an out-of-scope write command. Record whether the refusal came from the gateway, the device or the cloud tenant. If the industrial endpoint cannot differentiate operations, design a compensating site route instead of asserting that a portal role is sufficient.
Conduct the supplier departure rehearsal
Assume the original maintenance contractor is replaced during a plant expansion. The incumbent's technicians may still have accounts, stored certificates and knowledge of the old gateway's external address. The operator should identify a staged exit: prepare replacement support access, reconcile open work orders, transfer engineering documentation under approved controls, rotate site connector secrets and invalidate the retired vendor's tenant roles. Verify that the replacement provider can perform one approved simulated check while the original credentials fail. Include an offline gateway restored from an old image, since it could silently reintroduce a trusted certificate when it reconnects. A signed supplier exit is not complete until the site-side technical boundary supports it.
Confirm local recovery ownership
The site should keep a validated, access-controlled copy of the necessary operating and recovery instructions so that a cloud support outage does not make local staff dependent on the unavailable vendor portal. Specify who can authorise an emergency vendor session, whether plant alarms remain visible while external access is suspended, and how all temporary credentials are withdrawn after the task. Rehearse only safe simulated functions. Any unresolved dependency on a remote command interface must be reviewed by engineering and safety personnel before the checklist is signed.
Site-access test cases for a tabletop
- An approved engineer reads diagnostic measurements for asset A during a scheduled window; the receiving system should associate the access with the work order and site approver.
- The same identity requests settings from asset B, outside its assigned zone; the simulator should reject the action even if the cloud portal could reach the gateway.
- A supplier account is disabled during an existing remote session; measure when site commands stop and whether stored credentials continue to work offline.
- The cloud platform becomes unavailable while production alarms are active; site personnel must retain local visibility and a documented safe method of obtaining urgent assistance.
- A retired connector is brought online from an old maintenance image; determine whether its certificate and tenant registration still permit a new session and who will rotate them.
Handover to the industrial risk owner
An industrial risk owner should receive the test scope, engineering restrictions, successful maintenance demonstration, denied out-of-zone request, observed expiry or revocation delay, and known dependencies on the supplier cloud. Note any functions untested for safety reasons and the planned independent assessment. Never replace that record with a blanket statement that the SaaS product is 'OT secure'. The question is whether the specific support path does only the approved work and whether the operator can safely withdraw it when required.
Sources and further reading
- https://www.cyber.gov.au/publication/principles-of-operational-technology-cyber-security
- https://www.cyber.gov.au/publication/essential-eight-maturity-model
- https://www.nist.gov/cyberframework
Work with Next Defence
Next Defence can support engineering-led OT access assessment, supplier session controls and safe remote-maintenance tabletop exercises.